System: GCC

GCC

Product description

Single-leaf, vertically and horizontally closing fire protection closure for wall openings of web-bound Conveyor systems; separated and unseparated conveyor technology in the closing area.

TypeFire protection closure as part of track-bound conveyor systems
VerificationETA-16/0851 European Technical Assessment | VKF Technical Information No. 32235
Closing directionFrom top to bottom | from left to right | from right to left
Fire resistanceEI1 90 | tested according to DIN EN 1366-7:2004 | classified according to EN 13501-2:2007
Closing cyclesC4 | Number of closing cycles 100,000 | vertical closing direction
C5 | Number of closing cycles 200,000 | horizontal closing direction
Reopeningmotor
Conveyor systemInterrupted conveyor system | Inclined conveyor system | Continuous belt conveyor system | Continuous transfer carriage | Continuous suspension chain conveyor system | Continuous roller conveyor system | Continuous conveyor system
Visible surfacesAttachment parts:
galvanised | coated in RAL colour | stainless steel 1.4301 (V2A)

Fest panel and damper blade:
untreated fire protection boards | painted with dispersion paint in a similar RAL colour | galvanised sheet metal cladding | sheet metal cladding stainless steel 1.4301 (V2A) | sheet metal cladding coated in RAL colour

Size dimensions and system design

Due to the combination of classifications or the ratio of clear system width to clear system height, the stated maximum dimensions may be reduced and the dimensions of the enclosure and guide rails may vary. The specifications on the quotation apply.

Component (supporting structure) in which the closure may be installedachievable Fire resistance class
clear wall opening
largest width LBgreatest height LHlargest surface
Solid high-density wall, masonry or solid concrete with a total density of ≥ 800 kg/m3 and a thickness ≥ 150 mmEI1 90
EI2 90
3.600 mm4.200 mm10,0 m2
Solid low-density wall, aerated concrete with total density of ≥ 450 kg/m3 and thickness ≥ 150 mmEI1 90
EI2 90
3.600 mm4.200 mm10,0 m2


The installation situation must comply with the building code requirements of the country of installation. The fire resistance of a ceiling or wall support structure and the adjacent components must at least correspond to that of the fire protection closure. Proof of the stability and serviceability of the adjacent walls and components must be provided under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN1366-7:2004 or EN1363-1:2020. The fire protection system must not be subjected to any additional loads other than its own weight, even in the event of fire.

Vertical system structure

Fibershield-I
a = 155 | c = 570 | f = 70 | s = 51

System structure horizontal

Fibershield-I
b = 260 | c = 270 | d = 500 | f = 70 | i = 425 | s = 51