SYSTEM: FIBERSHIELD® | SYSTEM FIBERSHIELD®-S

  • Fibershield-S

Product description

Fire protection that goes around the corner: The base of the closure can be rectangular or polygonal with angles between 30° and 150°. Despite the formation of corners, no additional support elements are required. In addition to a closed polygonal shape, open systems can also be realised, which are fixed to the wall body with special guide rails. With the help of the standard "Gravigen" drive system, the fire protection curtain can be closed without external energy.

With Fibershield®-S, sophisticated sealing geometries can be realised and at the same time the requirements for room sealing over 90 minutes can be fulfilled.

ConstructionCircumferential non-insulating fire curtain
ProofIBS 08062416
closing directionfrom top to bottom
Fire resistanceE 30 - EW 90 | tested according to EN 1634-1:2014+A1:2018 | classified according to EN 13501-2:2016
Closing cyclesC0, C, C1 | tested according to EN 12605:2000-08 and EN 12604:2017-12 | classified according to EN 13501-2:2016
Fire behaviour of the textileA2-s1, d0; B-s1, d0; E-d2 | tested according to ISO 1716 and EN 13823 or ISO 11295-2 | classified according to EN 13501-1:2018
Environmental conditionsNot taken into account are special environmental conditions (e.g. humidity > 80 %, ambient temperature < 5 °C and temperature < 5 °C and > 40 °C, wind loads, etc.)
Visible surfacesgalvanised
RAL, smooth, semi-gloss, standard colour
NCS, standard colour
Fibershield-S

Legend system components:
1 = Smoke detector
2 = Casing
3 = Side guids
4 = Tubular motor
5 = Fabric
6 = Closing element
7 = Coil
8 = Control module
9 = Control with operating unit
10 = Manual release
SL = System length

Constructive system design (System drawing)

Fabric System widthDrop length (AL)t (mm)h (mm)
Ecotex 1100 A2< 50 m< 3 m490125
Ecotex 1100 A2< 50 m> 3 m - ≤ 6 m490225
Heliotex 9 EW 90< 50 m≤ 2,2 m490125
Heliotex 9 EW 90< 50 m> 2,2 m - ≤ 4,5 m490225
Heliotex 9 EW 90< 50 m> 4,5 m - ≤ 6 m490450

Closing strips


Closing strips Fibershield-S
Standard
Closing strips Fibershield-S
Sonder
With light spots or light strip

Casing Standard


Fibershield-S Gehäuse
Casing (open)
h = from table
t = 490 mm

d = 290 mm
Fibershield-S Gehäuse
Casing (closed)
h = from table
t = 490 mm

d = 290 mm

Casing Special


Fibershield-S Casing
Casing EI (open)
h = 240 mm
t = 490 mm

d = 290 mm
Fibershield-S Casing
Casing EI (closed)
h = 240 mm
t = 600 mm

d = 560 mm
Fibershield-S Casing
Locking equipment (optional)
h = 125 mm
t = 490 mm

d = 290 mm
S = Infrared security

Guide rails


Guide for open polygons
Guide for open polygons
a = 117 mm
b = 278 mm