    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • References
  • Theme worlds
  • News
  • Contact
Produkt - Moducoil

Stoebich Smoke Curtain M

Product Description

Prefabricated single modules are linked into a complete smoke protection curtain unit in any length. Standard unrolled lengths up to 275.59" Designd for time class and temperature loads D = 1,112°F. As standard with a 'Gravigen' drive sytsem, i.e. closes without external power source, fire-resistant cables are not necessary. Durable drive systems suitable for high cycle numbers up to 10,000 cycles with approved brakes. Module-like assembly of the winding casing above or next to each other. Connected closure strip above all modules. Can be combined with sping-loaded closure strip. Also suitable (approved) as a floor-closing smoke curtain. Optionally with integrated passage doors in floor-closing curtains. Alternatively with lateral guide rails.

Moducoil

construction type

textile smoke curtain

proof

- Z - 56. 429 - 916

closing direction

from top to bottom

classifications according to DIN EN 12101-1

Klassifizierung nach DIN EN 12101-1

Constructive structure - Einzelmodul

1 Rauchmelder 2 Gehäuse 3 Textil 4 Abschlussleiste 5 Wickel mit Rohrmotor 6 Ansteuerungsmodul 7 Steuerung mit Bedieneinheit 8 Handauslöser


1 Rauchmelder 2 Gehäuse 3 Textil 4 Abschlussleiste 5 Wickel mit Rohrmotor 6 Ansteuerungsmodul 7 Steuerung mit Bedieneinheit 8 Handauslöser

system width (SB)

drop length (AL)

t

h

≤ 5 m

≤ 4,5 m

150 mm

150 mm

≤ 5 m

> 4,5 m - ≤ 7 m

185 mm

185 mm

> 5 m - ≤ 7 m

≤ 4,5 m

185 mm

185 mm

Constructive structure - Multi-module, above each other)

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

system width (SB)

drop length (AL)

t

h

> 7 m

4,5 m

160 mm

280 mm

> 7 m

4,5 m - ≤ 7 m

195 mm

350 mm

Constructive structure - Multi-module, next to each other)

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

system width (SB)

drop length (AL)

t

h

> 7 m

4,5 m

250 mm

150 mm

> 7 m

4,5 m - ≤ 7 m

320 mm

185 mm

side guides

Wand

a 80 mm b 70 mm

Laibung

a 80 mm b 70 mm

Niesche

a 80 mm b 70 mm aN 85 mm bN 80 mm

housing

Standard

Single smoke protection (wall)

Single smoke protection (ceiling)

Modular smoke protection (wall/above one another)

Modular smoke protection (ceiling/above one another)

Modular smoke protection (ceiling/next to each other)

Modular smoke protection (wall/next to each other)

alternatives for installation

installation to the wall

installation to the ceiling

installation over suspension