• EN
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • References
  • Theme worlds
  • News
  • Contact
Product - Fibershield-S

Fibershield®-S

The space creating textile fire protection curtain that leads around the corner

Product description

Fire protection that leads around corners: The floor space of the closure can be realised in a rectangular and polygon-shape with angles between 30° and 150°. No support elements are required despite the corner design. In addition to a closed polygon shape, open systems can also be realised that close against the wall by installing special guide rails. The fire protection curtain can be closed without any external energy by means of the 'Gravigen' drive system that is included as standard. The Fibershield-S complex allows for complex sealing geometries to be realised, while also complying with the requirement of closing off a space for more than 90 minutes.

Fibershield-S

Type

Textile fire protection curtain

Achievable protection goals

EI - with fire load free zone • EW 90 • EI - with sprinklers

Fabric

Ecotex 1100 A2 • Heliotex

Fire load free zone

Protex/Ecotex: EI 30/60/90min 100/150/200 cm • Heliotex: EI 30/60/90min 20/30/50 cm

Verification

IBS 08062416 • UL 10 (b) (2009) • UL 10 (c) (2009) • UL 10 (d) (2009) • NFPA 252 (2012)

Closing direction

From top to bottom

Closing cycles

C1

Constructive system design - System drawing

1 Smoke detector 2 Casing 3 Side guids 4 Tubular motor 5 Fabric 6 Closing element 7 Coil 8 Control module 9 Control with operating unit 10 Manual release SL System length


1 Smoke detector 2 Casing 3 Side guids 4 Tubular motor 5 Fabric 6 Closing element 7 Coil 8 Control module 9 Control with operating unit 10 Manual release SL System length

Fabric

System width

Drop length (AL)

t

h

Ecotex 1100 A2

< 50 m

< 3 m

490 mm

125 mm

Ecotex 1100 A2

< 50 m

> 3 m - ≤6 m

490 mm

225 mm

Heliotex EW 90

< 50 m

< 2.2 m

490 mm

125 mm

Heliotex EW 90

< 50 m

> 2.2 m - ≤2.5 m

490 mm

225 mm

Heliotex EW 90

< 50 m

> 4.5 m - ≤6 m

490 mm

450 mm

Closing strips

Standard

Standard

Special

With light spots or light strip

Casing

Standard

Casing (open)

Casing - Casing (open)

h from table d 290 mm t 490 mm

Casing (closed)

Casing - Casing (closed)

h from table d 290 mm t 490 mm

Special

Casing EI (open)

 - Casing EI (open)

h 240 mm d 560 mm t 600 mm

Casing EI (closed)

 - Casing EI (closed)

h 240 mm d 560 mm t 600 mm

Locking equipment (optional)

 - Locking equipment (optional)

h 125 mm d 290 mm t 490 mm S Infrarot Sicherung

Guide rails

Standard

Guide for open polygons

Guide rails - Guide for open polygons

a 117 mm b 278 mm