• EN
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • References
  • Theme worlds
  • News
  • Contact
Product - Moducoil

Moducoil

The standard smoke apron in a modular design

Product description

Prefabricated individual modules are lined up as a unit to form a complete smoke apron up to any lengthStandardised drop lengths up to 7 m Designed for the time class and temperature loads D = 600 °C As standard with "Gravigen" drive system i.e. closing without external energy, fire-resistant cables are not necessaryRobust drive systems, suitable for a high number of cycles up to 1,000 cycles with approved locking devices Modular mounting of the winding casings on top of or next to each otherConnected closing strip across all modules Also suitable (approved) for use as a floor-closing smoke apron and with lateral guide rail option.

Moducoil

Type

Textile smoke apron

Proof of usability

UL 1784

Verification

- Z - 56. 429 - 916 • CE according to DIN EN 12101-1

Closing direction

From top to bottom

Closing cycles

1,000 cycles according to DIN EN 12101-1

Classification

D 120 • DH 30 • Classification according to DIN EN 12101-1

Triggering

Approved hold-open system • To be provided on site

Constructive system design - Single module

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

System width

Drop length

t

h

≤ 5 m

≤ 4,5 m

150 mm

150 mm

≤ 5 m

> 4,5 m - ≤ 7 m

185 mm

185 mm

> 5 m - ≤ 7 m

≤ 4,5 m

185 mm

185 mm

Constructive system design - Multiple module, above each other

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

system width (SB)

drop length (AL)

t

h

> 7 m

4,5 m

160 mm

280 mm

> 7 m

4,5 m - ≤ 7 m

195 mm

350 mm

Constructive system design - Multiple module, next to each other

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

System width

Drop length

t

h

> 7 m

4.5 m

250 mm

150 mm

> 7 m

4.5 m - ≤ 7 m

320 mm

185 mm

Guide rails

Standard

Wall

Guide rails - Wall

a 80 mm b 70 mm

Embrasure

Guide rails - Embrasure

a 80 mm b 70 mm

Niche

Guide rails - Niche

a 80 mm b 70 mm aN 85 mm bN 80 mm

Casing

Standard

Single smoke protection (wall)

Single smoke protection (ceiling)

Wall/above one another

Ceiling/above one another

Ceiling/next to each other

Wall/next to each other

Casing installation options

Wall mounting

Ceiling mounting

Suspension mounting

Closing strips

Standard

Standard

Standard

Special

Spring-loaded closing strip

Spring-loaded closing strip